Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) APPROVE TO CLOSE | |
| 07/22/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :new electric for plug mold to be added to plans need location and circuit and loads - revised plans to be stamped by cot where is elec to counter as per plans? missing cover plates boxes more than 1/4" from box to surface - to have approved extender rings RECEPTACLE FULL OF EXCESS PAINT NEW RECEPTACLES AS PER PLAN AT INSTALLATION JUNCTION BOXES OPEN IN CEILING SUPPORT M/C CABLE AS PER CODE |