Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM02488
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/28/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) BOND JUNCTION BOXES AS PER 250-148. 2) WE HAVE MORE OUTLETS ON CIRCUIT 11 THAN AS PLANS. ALSO PLANS STATE EXISTING FROM NEW AS FOR CIRCUITS. 3) MISSING RECEPTACLE COVERS UNDER DESK. 4) TRACK LIGHTING IS NOT ON PLANS - SUPPORT WITH SUPPORT WIRES AND SUPPORT M/C CABLE AS PER CODES. 5) SUPPORT CONDUIT ABOVE PANEL AS PER CODE AND TIGHTEN LOOSE FITTINGS. 6) A GROUND BAR IS NEEDED. GROUND HAS A SHEET METAL SCREW AND MULTIPLE TERMINATIONS UNDER LUG. |
|
06/11/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) AS PER BLDG INSPECTORS WRITE-UP ON 6/9/04 (ELECTRIC PLANS ARE NEEDED) |
|
06/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |