Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/03/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 07/28/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) RISER PIPE REQUIRED TO BE MINIMUM 2 1/2" IMC 2) RISER CONDUCTORS SHOULD BE COPPER 3) RISER CONDUCTOR INSULATION MUST BE SUN LIGHT RESISTANT (STAMP ON CONDUCTOR INSUALTION) |