Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T04CM02457
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2004 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
| 10/15/2004 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :*/ 1) NO ACCESS, BLDG LOCKED 4:20 PM | |
| 09/24/2004 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :*/FROM EXIST. METER NEW SUB METER 1" INSTALLED TIES INTO 1 1/2 YARD LINE TO BACK FLOW DEVICE & BUILDING OK PENDING REVISED CITY APPROVED PLAN OF THIS INSTALLATION. | |
| 09/13/2004 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* H20 PIPING 60 PSI AIR TEST OK. WASTE & VENT THRU ROF WATER TEST OK. CALL IN INSPECTION FOR VIEWING OF CLOSET FLANGES PRIOR TO SETTING OF STOOLS | |
| 08/31/2004 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :*/PARTIAL WATER TEST ON 4" BUILDING SEWER NOW TO TIE INTO 10" CLAY PARTIAL APPROVAL 1)HAVE 03055 PLB SEWER & HCS CONNECTION ADDED TO PERMIT CARD 2)HAVE REVISED CITY APPROVED PLAN FOR ACTUAL INSTALLATION OF NEW BUILDINT SEWER FROM 2-WAY CLEAN OUT TO TIE INTO EXISTING 10" CLAY. 1 1/2 COPPER FROM NEW MOTOR LOCATION TO BACKFLOW DEVICE SILVER SOLDORED? 60PSI AIR TEST OK 1)PLEASE CALL IN 03040 INSPECTION FOR THIS AT LATTER DATE |