Permit: T04CM02457

Parcel: 13510150R

Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Date Description Inspector Results Comments
12/03/2004 PLUMBING - PROGRESS Approved IVRS - Inspection :*
10/15/2004 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*/ 1) NO ACCESS, BLDG LOCKED 4:20 PM
09/24/2004 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*/FROM EXIST. METER NEW SUB METER 1" INSTALLED TIES INTO 1 1/2 YARD LINE TO BACK FLOW DEVICE & BUILDING OK PENDING REVISED CITY APPROVED PLAN OF THIS INSTALLATION.
09/13/2004 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :* H20 PIPING 60 PSI AIR TEST OK. WASTE & VENT THRU ROF WATER TEST OK. CALL IN INSPECTION FOR VIEWING OF CLOSET FLANGES PRIOR TO SETTING OF STOOLS
08/31/2004 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*/PARTIAL
WATER TEST ON 4" BUILDING SEWER NOW TO TIE INTO 10" CLAY
PARTIAL APPROVAL
1)HAVE 03055 PLB SEWER & HCS CONNECTION ADDED TO PERMIT CARD
2)HAVE REVISED CITY APPROVED PLAN FOR ACTUAL INSTALLATION OF NEW BUILDINT SEWER FROM 2-WAY CLEAN OUT TO TIE INTO EXISTING 10" CLAY.
1 1/2 COPPER FROM NEW MOTOR LOCATION TO BACKFLOW DEVICE SILVER SOLDORED? 60PSI AIR TEST OK
1)PLEASE CALL IN 03040 INSPECTION FOR THIS AT LATTER DATE