Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 10/08/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :TIGHTEN FLEX FITTINGS TO UPS & CONNECTORS FILL UNUSED OPENING IN WIRE MOLD RACEWAYS PLANS CIRCUITS HAVE GREATLY CHANGED - PLEASE SUBMIT REDLINES FOR STAMPED APPROVAL - CIRCUIT & PANEL SCHEDULES PLEASE HAVE ELECTRICIAN PRESENT TO OPEN UP SERVICE EQUIPMENT |
|
| 09/14/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/ 1) OK FLOOR BOXES AND WALLS ROOM #107 2) AREAS OCCUPIED WITHOUT INSPECTIONS AGAIN #114 AND #115 | |
| 08/23/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/PARTIAL- OK 8 RECTANGULAR FLOOR BOXIES & CONDUITS ROM #114? 1) PROTECT PVC AT WALLS |
|
| 08/03/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/ 1) OK 7 FLOOR BOXES AND CONDUIT |