Permit: T04CM02436

Parcel: 133040170

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM02436

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/28/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH ITEMS TO EXTERIOR AND SERVICE
2) OK TEMP C OF O-SUBJECT TO DETERMINATION OF S. LONG
08/12/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CEILING TO BE OPENED FOR INSPECTION
2) TILES CLOSED WITHOUT INSPECTIONS
3) AN APPROVED EXTENDER RING IS NEEDED FOR BOXES MORE THAN Q/4 FROM BOX TO SURFACE IN NON COMBTUSTIBLES 370.20 AND 314.20
4) FIXTURES TO BE AS PER PLANS
5) TIGHTEN LOOSE LOCK NUTS AND BOND AROUND CONCENTRICS
6) LABEL DISCONNECT AND PANEL COVER
7) SES NEEDS PLANS REVISED AND 3RD PARTY CERTIFICATION FOR TAP OF BUSSES
8) STRAP GROUNDING ELECTRODES OR CONDUCTOR
9) TIGHTEN LOOSE SEAL TITE FITTINGS AND PROTECT FROM SHARP METAL EDGES SUPPORT OVER 4' IN LENGTH
10) FILL UNUSED OPENINGS DISCONNECTS
11) TIGHTEN LOOSE FITTINGS
12) LABEL DISCONNECTING MEANS
13) SHEET METAL SCREWS NOT APPROVED FOR GROUNDING 250.8
08/11/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) FINISH WORK
08/10/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) FIXTURES TO BE ATTACHED TO GRID 410.16 IF MANUFACTURE CLIPS ARE USED THEY MUST BE EFFECTIVE. IF SCREWS ARE USED 4 ON CORNERS OR 2 ON CENTER
2) PLEASE VERIFY CONDUCTOR FILL FOR JUNCTION BOXES
3) SEAL TITE TO BE SUPPORTED AS PER CODE
4) FINISH MAKE UP
5) NEED PREVIOUS INSPECTION REPORT ON SITE
06/13/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK WALLS EXCEPT AS NOTED.
06/03/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio . 1) JUNCTION BOXES TO BE ACCESIBLE. 2) PLASTER RING TO SEAT ON BOX NO SPACERS. 3) EXTEND ALL BOXES TO SURFACE 370-20 4) REMOVE EAST WALL FOR INSPECTION OF BOXES. A REFEE HAS BEEN ACCESS PER ADMINISTRATIVE CODES.
06/01/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE FITTINGS
2) SUPPORT CONDUIT AS PER CODE
3) TIGHTEN PLASTER RING COVER
4) REMOVE DRYWALL ON SURFACE MOUNTED CONDUITS TO INSPECT
04/14/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* NO ONE ON SITE-WHAT IS TO BE INSPECTED?
03/24/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK 1ST LIFT. 1) TIGHTEN LOOSE CONNECTORS AND COUPLINGS
01/26/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK #4 TO REBAR OK 2"CONDUIT STUB FOR POWER 1) PLEASE ADD 02005 TO PERMIT AND 02010