Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM02436
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/28/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH ITEMS TO EXTERIOR AND SERVICE 2) OK TEMP C OF O-SUBJECT TO DETERMINATION OF S. LONG |
|
| 08/12/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CEILING TO BE OPENED FOR INSPECTION 2) TILES CLOSED WITHOUT INSPECTIONS 3) AN APPROVED EXTENDER RING IS NEEDED FOR BOXES MORE THAN Q/4 FROM BOX TO SURFACE IN NON COMBTUSTIBLES 370.20 AND 314.20 4) FIXTURES TO BE AS PER PLANS 5) TIGHTEN LOOSE LOCK NUTS AND BOND AROUND CONCENTRICS 6) LABEL DISCONNECT AND PANEL COVER 7) SES NEEDS PLANS REVISED AND 3RD PARTY CERTIFICATION FOR TAP OF BUSSES 8) STRAP GROUNDING ELECTRODES OR CONDUCTOR 9) TIGHTEN LOOSE SEAL TITE FITTINGS AND PROTECT FROM SHARP METAL EDGES SUPPORT OVER 4' IN LENGTH 10) FILL UNUSED OPENINGS DISCONNECTS 11) TIGHTEN LOOSE FITTINGS 12) LABEL DISCONNECTING MEANS 13) SHEET METAL SCREWS NOT APPROVED FOR GROUNDING 250.8 |
|
| 08/11/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FINISH WORK |
|
| 08/10/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FIXTURES TO BE ATTACHED TO GRID 410.16 IF MANUFACTURE CLIPS ARE USED THEY MUST BE EFFECTIVE. IF SCREWS ARE USED 4 ON CORNERS OR 2 ON CENTER 2) PLEASE VERIFY CONDUCTOR FILL FOR JUNCTION BOXES 3) SEAL TITE TO BE SUPPORTED AS PER CODE 4) FINISH MAKE UP 5) NEED PREVIOUS INSPECTION REPORT ON SITE |
|
| 06/13/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS EXCEPT AS NOTED. | |
| 06/03/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio . 1) JUNCTION BOXES TO BE ACCESIBLE. 2) PLASTER RING TO SEAT ON BOX NO SPACERS. 3) EXTEND ALL BOXES TO SURFACE 370-20 4) REMOVE EAST WALL FOR INSPECTION OF BOXES. A REFEE HAS BEEN ACCESS PER ADMINISTRATIVE CODES. |
|
| 06/01/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE FITTINGS 2) SUPPORT CONDUIT AS PER CODE 3) TIGHTEN PLASTER RING COVER 4) REMOVE DRYWALL ON SURFACE MOUNTED CONDUITS TO INSPECT |
|
| 04/14/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO ONE ON SITE-WHAT IS TO BE INSPECTED? | |
| 03/24/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST LIFT. 1) TIGHTEN LOOSE CONNECTORS AND COUPLINGS | |
| 01/26/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK #4 TO REBAR OK 2"CONDUIT STUB FOR POWER 1) PLEASE ADD 02005 TO PERMIT AND 02010 |