Permit: T04CM02433

Parcel: 11619227A


Addresses:

255 N GRANADA AV 11


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM02433

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :* CLOSET FLANGES OK
03/11/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/10/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTRACTOR HAS COVERED/CONCEALED PIPING BEFORE INSPECTION. INSPECTOR WILL NOT ACCEPT REMOVING INSULATION DURING INSPECTION. EXPOSE ALL PIPING AND FITTINGS FOR INSPECTION
2) NO TEST ON PVC
3) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP
4) VENT FITTINGS BELOW FLOOD RIM TO BE DRAINAGE FITTINGS
5) INSPECTION STOPPED
03/03/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/28/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/15/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/1)YARDWATER CONNECTION AT BLDG OK TO COVER 2)MAY NOT USE PVC FEMALE THREADED FITTING FOR WATER PIPING
11/22/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :* 6" SDR 35 X 6" SCH 40 PVC SEWER CONNECTION OK. COVER.