| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/09/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND METAL PROCH ELECTRIC BOX 2) ONCE ALL PLUMBING COMPLETE TO CLOTHES WASHER; WATER TEST BOTH SUPPLY AND DRAIN LINES 3) WASHER COPPER LINES TO BE ? FITTINGS OR TO BE ACCESSIBLE 4) CLOTHES WASHER DRAIN AND SUPPLY LINES NOT TO CODE 5) INSTALL BANG PLATES ALL ELECTRIC WIRES THROUGH WOOD LESS THAN 1 1/4" FROM EDGE 6) REMOVE EXISTING TRAP, EXTEND 2" LINE TO NEW LOCATION, INSTALL NEW TRAP AND STAND PIPE |
|
| 12/07/2004 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - Ri canceled | |
| 11/09/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PLAN CALLS FOR 30 AMP #10 WIRE A/C UNIT 2) GROUND ALL METAL ELECTRIC BOXES 3) PLAN CALLS FOR 2 OUTLETS WEST WALL AND 4 OVER HEAD LIGHTS 4) FILL ALL UNUSED OPENING IN ELECTRIC BOXES 5) WILL NEED TO DO SOMETHING WITH EXISTING LIGHT ON SOUTH WALL (EITHER EXTEND OUT TO NEW WALL SURFACE OF ELIMINATE) 6) CLOTHES WASHER TO BE 20 AMP #12 WIRE CIRCUIT 7) DRYER NOT WIRED YET 8) CLOTHES WASHER DRAIN LINE TO BE TIED INTO EXISTING AT EXISTING LOCATION 9) INSTALL BANG PLATES ELECTRIC WHERE SHEETROCK NAIL MIGHT PENETRATE 10) INSTALL ELECTRIC IN WALL AT EXIT LIGHT 11) CLOTHES WASHER RELOCATE NOT ON PLAN (NO PLUMBING ONE PERMIT CARD) |