Permit: T04CM02417

Parcel: 120071980

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/21/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/19/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE CORRECT DRAINAGE WITH TEST ON BATH TUB DRAINS.
2. SEE NOTE #3 FROM 2/28/07 INSPECTION SHEET ABOVE
3. HAVE NEW WATER HEATER ADDED TO PERMIT AND PROVIDE CORRECT TEMPERATURE & PRESSURE RELIEF DRAIN OR CORRECT INSTALLATION WITH CITY SIGNED PETITION OF APPEAL FOR ALTERNATE FORM OF TEMPERATURE AND PRESSURE RELIEF ON SITE.
4. LAUNDRY BOX WATER SUPPLY TO HAVE WATER HAMMER ARRESTORS FOR HOT & COLD SUPPLY.
5. DISHWASHER DRAIN HOSE TO HAVE HIGH LOOP AND BE CLAMPED AT THAT POINT.
6. SHALL PROVIDE LISTING & INSTALLATION INFORMATION ON WALL HEATERS IN (2) BEDROOMS FOR DIRECT VENTING AND CLEARANCES FROM OPENABLE WINDOWS FOR POSSIBLE SAFETY ISSUES.
7. SHALL RETEST GAS SYSTEM
8. HOSE BIBS REQUIRED WITH TAMPER SCREWS BROKEN OFF.
02/28/2007 PLUMBING - INTERMEDIATE Partial Approval 1) WASHER BOX AND KITCHEN OK. 2) DRAIN FROM CENTRAL RAISED TUB MUST BE PROPERLY TIED TO UNDREGROUND WASTE. IT MAY NOT ATTACH TO TRAP ARM OF ANOTHER TUB. 3) CAP FUNNEL ATTACHMENT BY WATER HEATER. TPRV DISCHARGE AT BACK OF CLOSET OK. 4) WATER CLOSET SIDE CLEARANCE OF LESS THAN 15" APPROVED BY BUILDING OFFICIAL
06/26/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*