Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM02404
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) PAINT ALL ROOF VENTS 2) PROVIDE ROOF ACCESS FOR A/C UNIT 3) INSTALL DISHWASHER DRAIN LINE |
|
| 01/14/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/13/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ADDRESS ON HOUSE 2) ALL EXTERIOR OUTLETS MUST BE GFCI PROTECTED 3) LABEL ALL CIRCUITS IN ELECTRIC PANEL 4) CLEANOUTS MUST HAVE THREADED CAPS AND TRIM TO GRADE 5) OUTSIDE HOS BIBS MUST HAVE ANTI-SIPHON VALVES 6) KITCHEN NOT COMPLETE 7) BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS |