Permit: T04CM02383

Parcel: 138242270

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
10/07/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
10/06/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) TRUSS REPAIR NOT NAILED BETWEEN 8 AND 9 OR BELOW 7 AND NOT BEARING AT POINT 14 2) CHIMNEY CHASE CANNOT BEAR ON OSB MUST BE CLIPPED AT 4 CORNERS TO ROOF STRUCTURE 3) OK TO DRY IN DO NOT COVER FP CLIP OR TRUSS REPAIR
09/30/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) A-1 3 PT BEARING TRUSS NOT BEARING AT MID-POINT 2) A-2 TRUSSES NOT 3 PT BEARING 3) A-8 NOT BEARING MID-POINT 4) SW5 MISSING ANCHORS BEHIND FURNACE 5) GARAGE HOLDOWN AT SW5 NOT CONNECTED TO SHEARWALL 6) 4 X 6 POST MISSING REAR PORCH 7) PROVIDE CHIMNEY FRAME PLAN FOR AS BUILT WITH POSITIVE CONNECTION TO STRUCTURE