Permit: T04CM02376

Parcel: 136326440


Addresses:

10809 E SKY HIGH DR

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/15/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/11/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) BLOCK AROUND HVAC DUCTS AT GARAGE
2) MAINTAIN SUPPORT FOR H20 HEATER, UNDER OSB AT PLATFORM
3) HAVE SPRINKLER SYSTEM INSPECTED BY FIRE DEPARTMENT
4) NORTH BATH CAN LIGHT FLEX ELECTRIC TOUCHING CU. H20 LINE
5) NORTH EAST BATH OVERSPAN STUD SPACE, AT TOILET
6) DON'T LET CONDENSATE/T & P TERMINATION GET BURIED, THEY NEED A DRY WELL
7) PRESSURIZE H20 LINE
8) NEED A H20 BOND
9) NOTES FROM LAST INSPECTION NOT IN PLAN TUBE-DWV NO H20 TEST
10) BACKING VERT REFRIG/AREA INSIDE CORNER, F/BLKS MISSING
11) APPROVAL ON HANGER
12) FIRE PLACE CAULK AT LOG LITER PIPE
13) NAIL AND STRAP CANTILIEVER BEAMS
14) WET VENTING IS ONLY ALLOWED FOR TRAP ARMS SEE DRAWING FRONT PAGE, HALL BATH
15) FIRE BLOCK LID F/PLACE MASTER BED, DOES F/PLACE GET A LOW VOLTAGE CONTROL WIRE ?
16) LOOSE OUTLET MASTER BEDROOM
17) MASTER WINDOW CHECK GLASS
18) MISSED TWO H.D.
19) OUTLET JACUZZI ACCESS PANEL
20) LAV VENT 6" ABOVE FLOOD RIM
21) MISSED TWO H.D. N/BEDROOM (12) TOTAL
03/30/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*