Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 03/30/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* | |
| 02/24/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NEED DETAIL OF F/PLACE, AND HEADER AT F/PLACE. YOU HAVE A DBL. HANGER FOR BEARING RAFTERS BUT THEY AREN'T TIED TOGETHER ALL WEIGHT IS ON ONE JOIST. 2) NEED HANGER SIZES 3) FILL ALL HOLES OF SCHEWD HANGERS. 4) F/PLACE DETAIL TO SHOW CLR. TO COMBUSTIBLES AROUND THE F/PLACE. 5) HAVE TJI SIZE AT GARAGE, LONGEST ONES PUT ON PLAN | |
| 02/08/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) BEARING ENDS INSTALL H2.5'S 2) AIR GAP LEDGER AT CHIMNEY 3) YOU NEED A FIREPLACE DETAIL |