Inspection History Details
Inspection Status: Approved
Inspection History: ENGINEERING - FINAL
Permit Number - T04CM02372
Inspection Description - ENGINEERING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2006 | ENGINEERING - FINAL | Approved | CALL FOR FINAL GRADING | |
05/25/2006 | ENGINEERING - FINAL | Denied | DENIED, PUBLIC ACCESS HAS BEEN SEPARATED FROM CONSTRUCTION ACTIVITIES; HOWEVER DRAINAGE STRUCTURES FOR THE SITE ARE NOT COMPLETED AND SITE WORK IS NOT FINISHED. CONTACT THE BLDG. OFFICIAL FOR A POSSIBLE TEMP C OF O. |
|
05/22/2006 | ENGINEERING - FINAL | Denied | DENIED, SEE ITEMS #1-4 FROM THE C OF O INSPECTION ON 5/19/06. | |
05/17/2006 | ENGINEERING - FINAL | Denied | DENIED, SITE WORK NOT COMPLETED: 1) COMPLETE ALL DRAINAGE STRUCTURES PER PLAN, TO INCLUDE CATCH BASINS, ROOF DRAINS, SCUPPERS .... 2) PROVIDE PARKING AND ADEQUATE ACCESS TO BUILDING TO INCLUDE H.C. ACCESS FREE FROM OBSTRUCTIONS AND CONSTRUCTION ACTIVITIES. 3) COMPLETE AND APPROVE THE FINAL GRADING FOR PERMIT#T04BU01938. 4) PROVIDE AN ENVIRONMENT FREE FROM LIFE SAFETY HAZARDS AND SEPARATE FROM CONSTRUCTION ACTIVITIES. NOTE: HAND RAILS WILL BE REQUIRED FOR ANY RAMP OTHER THAN A CURB RAMP WITH A RISE GREATER THAN 6" OR LONGER THAN 72". (PER COT DEV STD 3-0.10, SECTION 4.2, SUBSECTION (F), RAMP SAFETY.) |