Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM02372
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. ABS VTR WATER TEST OK 3. COPPER WATER TEST OK 4. CLOSET FLANGES OK 5. ROOF DRAINS OK 6. OK TO COVER WALLS |
|
02/17/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PLAN APPROVED BY WILDAN AND ENGINEERED BY SMU SHOWS 2-2" METERS AND RBS SUPPLYING A 4" WATER MAIN - THE 4" MAIN IS CALCULATED AT 6FT/SEC - PROVIDE ENGINEERING TO SHOW THAT THE 2" RPS AND 2" PIPING AT RPS WILL NOT EXCEED THE MAX 8FT/SEC VELOCITY ALLOWED BY CODE. - 100 PSI TEST ON WATER PIPING ALL EXCEPT HB AT COL L.2. SECURES PIPING AT TOILET RM 119 - DWV WATER TEST PIPING THRU ROOF AT TR 117&118 OK |
|
02/15/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/06/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/24/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*CONTRACTOR REDLINED A REVISION TO THE PLAN ADDING A MOP SINK AND AN AUTOMATIC WASHER. OK TO COVER- SUBJECT TO REVISED APPROVED PLAN | |
10/10/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*UNDERGROUND INSIDE THE BLDG COMPLETE. |