Permit: T04CM02345

Parcel: 140324280

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM02345

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2004 FRAMING Approved IVRS - Inspection :*
08/09/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FIRE BLOCK MISSING AT KITCHEN WALL 2) LEAVE GABLE TRUSS AT GARAGE VISIBLE FOR INSPECTION UNTIL APPROVAL BY CITY OF TUCSON, EXT. CLIPS WILL BE APPROVED WHEN DETAIL IS APPROVED BY CITY OF TUCSON
08/07/2004 FRAMING Partial Approval IVRS - Inspection :*(1) DEAD WOOD TRUSSES NOT BRACED @ 10' O.C. (2) NO TRUSS DRAWINGS. (3) NO WATER ***. (4) CHECK FOR MISSING F(BLOCKING
08/02/2004 FRAMING Denied IVRS - Inspection :FRONT GABLE NOT COMPLETE
REAR GABLE NOT COMPLETE
NO TEST ON DWV
FLEX DUCT HANGING FROM TRUSSES - NAIL PROTECT CONDENSATE
CHECK STAPLE SPACING SOUTH EAST AREA
BLOWN FIREBLOCK AND SHEAR NOT COMPLETE BETWEEN BEDROOMS
NAIL PROTECT WATER LINES AT HALL BATH
STOPPED INSP