Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T04CM02345
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2004 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
08/31/2004 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :*/ 1) PROVIDE T22 GABLE TRUSS APPROVED BY CITY OF TUCSON NOT ON CALC'S | |
07/27/2004 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* PARTIAL PENDING T-22 TAN?? APPROVAL BY C.O.T | |
07/26/2004 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* | |
07/22/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ANCHOR BOLT UNDER WATER HEATER PLATFORM NOT TIGHT 2) GABLE TRUSS REAR NOT BEARING 3) DBL TOP PLATE CUT AT 2 X 6 WALL 4) NAIL PROTECT ELECTRICAL CONDUIT AT KITCHEN EXTERIOR WALL 5) KNEE WALL AT ENTRY NOT CLIPPED 6) TG TRUSSES NOT BRACED 7) CROSS BRACING NOT PER PLAN 8) CLIPS MISSING NAILS 9) VENTING NOT PER PLAN 10) GARAGE GABLE TRUSS NOT ON CALC'S |