Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM02344
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
10/05/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) COMPLY WITH FIG 17 INSTALL MANUAL AND PAGE 24 FOR FAU 2) NEG PITCH AT SECONDARY PAN |
|
10/04/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/29/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NO INSUALTION UNDER UNIT PLATFORM IN ATTIC 2) SECONDARY PAN HAS CONSTRUCTION DEBRIS IN IT, AND NEGATIVE PITCH FOR DRAINING 3) FAU DOOR WON'T CLOSE 4) REFRIGERANT LINE NOT INSULATED WITHIN 2 FEET FROM UNIT 4) INSULATION CERTIFICATE ON SITE DATED 8/16/04 ? INSULATION |