Permit: T04CM02327

Parcel: 133243700

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T04CM02327

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2004 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/10/2004 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ HORIZONTAL SECTIONS OF CONDENSATE DRAIN LINE MUST BE SUPPORTED MAX 4' SPACING. DO NOT USE T-BAR WIRE FOR SUPPORT. YOU CANNOT TERMINATE CONDENSATE INTO A SEWER VENT PIPE. RECALL FOR INSP. ROUGH DUCT DIFFUSERS AND EXHAUST ARE OK.