Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T04CM02265
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
11/17/2004 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*/REMOVE DIRT FROM UNTREATED JOIST | |
11/09/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) EXPOSE PLUMBING WHERE INDICATED 2) EXPOSE FTG AND HAVE PACHO METER TEST BY TESTING LAV TO CONFIRM REBAR IN FTG'S AND WALLS |
|
11/08/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950*/ 1) EXPOSE ALL FOOTINGS AND FOUNDATION TO A DEPTH OF 12" AND PROVIDE PROOF OF REINFORCING STEEL 2) UNTREATED WOOD IN FLOOR JOIST IN CONTACT WITH SOIL OR TO CLOSE PER CODE. REMOVE ALL FLOOR SHEATHING 3) REINFORCING STEEL CANNOT BE IN CONTACT WITH SOIL 4) PORCH FOOTINGS NOT PER 1/3 5) TRUSS T-25 MISSING "T" BRACE 6) TRUSS T-14 HAS BEEN SCABBED. PROVIDE APPROVED REPAIR DOCUMENT 7) STOPPED INSPECTION. TOO MANY ITEMS |