Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2004 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 11/24/2004 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :OK TO DRYIN BOTH ROOFS AND EXT WALLS NEED TRUSS REPAIR & DETAIL SHEAR TRANSFER |
|
| 11/22/2004 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :*/ 1) NEED A GUSSET PLATE ON TRUSS CUT FOR FIREPLACE 2) NEED A CRICKET FOR FIREPLACE 3) NO DETAIL FOR SHEAR CONNECTION TO TRUSSES 4) PER TRUSS DRAWINGS, NEED TO RAT RUNS CONTINOUS ON MAIN SCISSOR TRUSSES 5) NOT LABEL ON TRUSS DRAWINGS REF. VERT. DEFLECTION, AND AMOUNT OF DEFLECTION, REMOVE OR GAP REQUIRED AT BOTTOM CHORD TO TOP PLATES OF INTERIOR PARTITIONS 6) AT PORCHES USE DETAIL 7/8 FULL HT. BLK. NAILED TO ROOF 7) NEED STUDS AT REAR ARCH 8) WALKED BOTH ROOFS 9) GARAGE ROOF DECK OK 10) NEED X BRACING AT RIDGE AND 25' ON CENTER 11) INSTALL ALL FACIA |