Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM02249
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/18/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WATER TEST WASTE AND VENT THRU ROOF PER REVISED APPROVED PLAN 2) PROVIDE MINIMUM 50 PSI AIR TEST OK WATER TEST ON H20 PIPING 3) PROVIDE CORRECT SUPPORTS ON MID SPAN OF 2" VENTS AND 1/2 H20 TO TRAP PRIMER TEN MIL TAPE IS NOT APPROVED 4) IF YOU HAVE SODA DISPENSOR EQUIPMENT IT WILL REQUIRE H20 SUPPLY AND CORRECT BACKFLOW PROTECTION FOR FINAL |
|
08/08/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) APPROVED PLANS CALL FOR A 3" VTR AND VENT FOR FLOOR SINK TO CONNECT TO 3" VTR |
|
08/03/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL YOUR PIPING FOR APPROVED PLAN. CLEANOUTS TO BE INSTALLED IN DIRECTION OF FLOW. PLEASE MEET MINIMUM REQUIREMENTS OF 94 UPC UNIFORM PLUMBING CODE |