Permit: T04CM02249

Parcel: 12701001B


Addresses:

421 N ARCADIA AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM02249

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/18/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER TEST WASTE AND VENT THRU ROOF PER REVISED APPROVED PLAN
2) PROVIDE MINIMUM 50 PSI AIR TEST OK WATER TEST ON H20 PIPING
3) PROVIDE CORRECT SUPPORTS ON MID SPAN OF 2" VENTS AND 1/2 H20 TO TRAP PRIMER TEN MIL TAPE IS NOT APPROVED
4) IF YOU HAVE SODA DISPENSOR EQUIPMENT IT WILL REQUIRE H20 SUPPLY AND CORRECT BACKFLOW PROTECTION FOR FINAL
08/08/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) APPROVED PLANS CALL FOR A 3" VTR AND VENT FOR FLOOR SINK TO CONNECT TO 3" VTR
08/03/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL YOUR PIPING FOR APPROVED PLAN. CLEANOUTS TO BE INSTALLED IN DIRECTION OF FLOW. PLEASE MEET MINIMUM REQUIREMENTS OF 94 UPC UNIFORM PLUMBING CODE