Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM02247
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2004 | FRAMING | Approved | IVRS - Inspection :* | |
12/23/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NEED MORE NAILS IN HANGERS SMALL GIRDER (BOTH SIDES) AT FIREPLACE TRUSSES 2) INSTALL FIREPLACE SPARK PROTECTION AT HEARTH EXTENSION, HEARTH EXTENSION TO BE MINIMUM 16" 3) SEAL FIRE STOP METAL AND LOCK FIREPLACE FLUE TOGETHER AT JOINT 4) ZERO GAS PRESSURE TEST 5) LAUNDRY EXHAUST FAN NOT CONNECTED TO ROOF JACK 6) COMBUSTION AND RELIEF DUCTS IN DOORS NOT SUFFICIENT 7) COMBUSTION RELIEF DUCTS THRU ROOF, NEEDS TO GO UP THRU OSB INTO GARAGE GABLE AREA, NOT ENOUGH AIR WHERE INSTALLED NOW 8) FIRE CAULK FIREPLACE LOG/LITE WITH FIREPLACE CAULK 9) LEAVE TRUSS DRAWINGS TO CHECK BEARING AND RAT RUNS 10) SHEARWALLS REQUIRE A.B.'S AT EACH END, THEN 3/4 PTS 11) OUTLETS NOT ALLOWED UNDER KITCHEN COUNTER OVERHANG DIAMETER 12) A.B.'S REQUIRED AT EACH SIDE OF BOTTOM PLATE SPLICES 13) USE 16D COMMONS IN GIRDER TO TRUSS HANGERS 14) BANG PLATE ALL WIRES 15) LIGHTS IN CLOSETS COMPLY WITH CODE, DISTANCE TO SHELF 16) INSTALL 6 X 6 POSTS UNDER GIRDER ENDS 17) CHECK WITH PLAN, SMALL GIRDER BEARS ON WINDOW HEADER EAST SIDE 18) NEED DWV TESTED 19) TWO ROMEX HANGING FROM MASTER BATH CEILING, CHECK ALL FIXTURES |
|
12/10/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |