Permit: T04CM02247

Parcel: 140441230


Addresses:

8039 S FARMBELT DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM02247

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2004 FRAMING Approved IVRS - Inspection :*
12/23/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NEED MORE NAILS IN HANGERS SMALL GIRDER (BOTH SIDES) AT FIREPLACE TRUSSES
2) INSTALL FIREPLACE SPARK PROTECTION AT HEARTH EXTENSION, HEARTH EXTENSION TO BE MINIMUM 16"
3) SEAL FIRE STOP METAL AND LOCK FIREPLACE FLUE TOGETHER AT JOINT
4) ZERO GAS PRESSURE TEST
5) LAUNDRY EXHAUST FAN NOT CONNECTED TO ROOF JACK
6) COMBUSTION AND RELIEF DUCTS IN DOORS NOT SUFFICIENT
7) COMBUSTION RELIEF DUCTS THRU ROOF, NEEDS TO GO UP THRU OSB INTO GARAGE GABLE AREA, NOT ENOUGH AIR WHERE INSTALLED NOW
8) FIRE CAULK FIREPLACE LOG/LITE WITH FIREPLACE CAULK
9) LEAVE TRUSS DRAWINGS TO CHECK BEARING AND RAT RUNS
10) SHEARWALLS REQUIRE A.B.'S AT EACH END, THEN 3/4 PTS
11) OUTLETS NOT ALLOWED UNDER KITCHEN COUNTER OVERHANG DIAMETER
12) A.B.'S REQUIRED AT EACH SIDE OF BOTTOM PLATE SPLICES
13) USE 16D COMMONS IN GIRDER TO TRUSS HANGERS
14) BANG PLATE ALL WIRES
15) LIGHTS IN CLOSETS COMPLY WITH CODE, DISTANCE TO SHELF
16) INSTALL 6 X 6 POSTS UNDER GIRDER ENDS
17) CHECK WITH PLAN, SMALL GIRDER BEARS ON WINDOW HEADER EAST SIDE
18) NEED DWV TESTED
19) TWO ROMEX HANGING FROM MASTER BATH CEILING, CHECK ALL FIXTURES
12/10/2004 FRAMING Not ready for Inspection IVRS - Inspection :*