Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/19/2004 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - Ri canceled | |
| 08/19/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/PARTIAL- OK WALLS 1)PLANS ARE IN FOR TEVISION. NEED BY FINAL |
|
| 08/05/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) PLUMBING FITTINGS NOT FOR USE AS ELECTRICAL 2) SUPPORT CONDUITS AS PER CODE 3) GROUND CONDUCTOR TO BE 3/4 OF A TURN UNDER SCREW 4) TIGHTEN LOOSE FITTINGS 5) SUPPORT NM CABLE WITHIN 12" OF BOXES 6) PLANS TO BE REFLECTIVE OF WORK INSTALLED-YOU HAVE MORE RECEPTACLES AND SWITCHES THAN INDICATED ON PLAN, PLEASE REVISE PLANS AND HAVE STAMPED AND APPROVED 7) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 8) PERMANENT LABELING FOR EQUIPMENT NEEDED |