Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/11/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) OK FINAL |
| 06/07/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ FINISH 1 & 3 OF PREVIOUS INSP. |
| 05/28/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) CONDUIT SEALING TO BE AT ENTRANCE TO WALK-IN BOX NOT INSIDE JUNCTION BOX. 2) BREAKERS TO BE LISTED FOR USE BY MANUFACTURER. 3) FILL UNUSED OPENINGS ABOVE PANEL. 4) PLEASE PROVIDE ROOF ACCESS. |
| 05/25/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) DISCONNECTING MEANS NEEDED FOR CONDUIT INSIDE WALK-IN. 2) SEAL CONDUIT AT ENTRANCE TO BOX - INSIDE CONDUIT FOR TEMP DIFFERANCE. 3) RESUPPORT JUNCTION BOX AND CAP OFF EXPOSED CONDUCTORS. 4) MAINTAIN WORKING CLEARANCE IN FORNT OF PANELS - CAN NOT ACCESS. |