Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM02197
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK FINAL | |
06/07/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ FINISH 1 & 3 OF PREVIOUS INSP. | |
05/28/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) CONDUIT SEALING TO BE AT ENTRANCE TO WALK-IN BOX NOT INSIDE JUNCTION BOX. 2) BREAKERS TO BE LISTED FOR USE BY MANUFACTURER. 3) FILL UNUSED OPENINGS ABOVE PANEL. 4) PLEASE PROVIDE ROOF ACCESS. | |
05/25/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) DISCONNECTING MEANS NEEDED FOR CONDUIT INSIDE WALK-IN. 2) SEAL CONDUIT AT ENTRANCE TO BOX - INSIDE CONDUIT FOR TEMP DIFFERANCE. 3) RESUPPORT JUNCTION BOX AND CAP OFF EXPOSED CONDUCTORS. 4) MAINTAIN WORKING CLEARANCE IN FORNT OF PANELS - CAN NOT ACCESS. |