Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER PROOF COVER IN SHOWER CAN 2) CAULK EXTERIOR FIREPLACE PENETRATIONS 3) MAIN SERVICE 20 AMP BREAKER DBL LUGGED 4) PROVIDE ACCESS TO ROOF |
|
| 03/09/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUBMIT ALL AS BUILT CHANGES FOR APPROVAL 2) ADD ELECTRIC BOX EXTERIOR TO PLAN (FUTURE AC) 3) INSTALL CEILING FAN 4) GARAGE 110 OUTLETS TO BE GFCI 5) COMPLETE FIREPLACE FACING EXTERIOR 6) BEDROOM FIREPLACE TO HAVE EXTERIOR GAS COCK OUTSIDE OF UNIT 7) ANTI-SIPHON HOSE BIBS 8) INSTALL H20 HTR PTR TO EXTERIOR 9) INSTALL H20 HTR DRAIN PAN DRAIN TO ? 10) ELECTRIC PANELS NOT PER PLAN 11) STOPPED INSPECTION |