Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* APPROVED | |
| 02/07/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DUCT SMOKE DETECTOR NOT SHUTTING OFF FAN. ALL OTHER CORRECTIONS HAVE BEEN MADE | |
| 01/24/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE SUN SHIELD OVER CANVAS CONNECTORS. PROVIDE CARBON DIOXIDE SENSOR. 1/2" I.D GAS FLEX CONNECTOR NOT ADEQUATE FOR 250.000 BTU. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE. PROVIDE A DUCT SMOKE DETECTOR AS PER PLANS |