Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/24/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTA HOT NOT TO BE CORD & PLUG CON??. 2) TIGHTEN LOOSE FITTINGS AT " SES". 3) ONLY ONE CONDUCTOR PER TERMINAL CONNECTION. 4) FINISH #1 PREVIOUS INSPECTION. 5) PLEASE LABEL TRANSFORMERS. OK TEMP C OF O | |
| 12/08/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) APPROVED EXTENDER RING NEEDED AT BOXES MORE THAN 1/4" FROM BOX TO SURFACE 370.20/?.20 2) FINISH CLOSET UNDER STAIRS, DRESSING ROOM LIGHTING 3) INSTALL ALL MISSING PLATES 4) GROUND STRIP LIGHT FIXTURES 5) BOND JUNCTION BOX FOR CONTRACTOR 6) CORRECTLY TERMINATE NEUTRAL TO CONTACTOR 7) PLEASE HAVE ELECTRICIAN PRESENT TO OEPN SERVICE EQUIPMENT AND PANELS |