Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2004 |
PLUMBING - PROGRESS |
|
Approved |
IVRS - Inspection :*/ 1) SOIL WTR TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN IS OK. 3) OK TO BACKFILL TRENCH. 4) OVERHEAD WTR DISTRIBUTION OK. |
| 06/17/2004 |
PLUMBING - PROGRESS |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 06/14/2004 |
PLUMBING - PROGRESS |
|
Partial Approval |
IVRS - Inspection :*/ H2O PIPING WTR TEST OVERHEAD AND IN WALL OK. 1) ADDITION OF 4TH FOOT SPA - POSSIBLY FUTURE - WILL REQUIRE CITY APPROVED DRAWING AND BACKFLOW PROTECTION ON H20. 2) DRAINAGE FOR FOOT SPAS WILL ALSO REQUIRE REVISED CITY APPROVED DRAWING OF CORRECT DRAINAGE OF FOOT SPAS. |
| 06/10/2004 |
PLUMBING - PROGRESS |
|
Not ready for Inspection |
IVRS - Inspection :*/ PROVIDE APPROVED DRAINAGE FITTING FOR FLOOR SINK VENT. DRAINAGE FOR FOOT SPAS IS APPROVED IN ERROR. PLEASE SUPPLY APPROVED METHOD OF DRAINAGE FOR THIS FIXTURE. |