Permit: T04CM02178

Parcel: 12615011C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM02178

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/15/2004 ELECTRIC - FINAL Not ready for Inspection 1) WALK-IN COOLER. ELECTRICAL FINAL HAS BEEN APPROVED BY RAY ON 10/27 BUT CONTRACTOR SAYS THEY WERE MISSING ONE WALK-IN
2) NEED DISCONNECTING MEANS WITH IN SIGHT OF EVAPORATOR UNIT IN WALK-IN (CIRCUIT B-14-16
10/27/2004 ELECTRIC - FINAL Partial Approval
10/26/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/1)SEAL WALK IN BOX AS PER 300.> - SILICONE IS NOT ALLOWED 2)PROTECT SEAL TILE WHERE PASSING THRU SHARP METAL EDGES 3)MARKING TO BE PERMANANT NOT PENCIL-COOLER DISC. 4)RECPICALEIS TO BE ACCESSABLE OR BLANKED OFF BEHIND BOOTHS 5)EMERGENCY LIGHTING NOT CIRCUITED AS PER PLANS