Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM02173
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/09/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NECESSARY CORRECTIONS NOT COMPLETE |
|
| 11/08/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) INSULATION CERTIFICATE? 2) SEAL AROUND TOILET BASE 3) COMPLETE GRADING 4) SECURE ELECTRIC SPRINKLER CONDUIT TO WALL 5) WHAT ARE WIRES PROTRUDING FOR WEST WALL EXTERIOR? 6) A/C DISCONNECT BOX WIRES INCORRECTLY COLOR CODED 7) POST TENSION TAG H20 SERVICE 8) LABEL ELECTRIC SERVICE NOT A H20 BONDED SYSTEM |
|
| 11/02/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) CANCELLED |