Permit: T04CM02123

Parcel: 125060250


Addresses:

2002 E 3RD ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/11/2005 FRAMING Approved IVRS - Inspection :*
1) COMPLETE WATER HEATER DOOR FRAMING
03/09/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
03/02/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) EXISTING BATHROOM, CEILING LIGHT FIXTURE ROMEX PULLED TO TIGHT, SECURE ROMEX 6" OF BOX, UNSHEATHED WIRE OUTSIDE BOX
2) NEED A 12 GAUGE WIRE 20 AMP CIRCUIT FOR BATH/OUTLET/RECEPTACLE
3) NAIL PROTECTION MISSING THRU OUT BATHROOM
4) BEAM BEARING FROM OTHER SIDE OF WALL, STUDS BELOW NOTCHED TO DEEP
5) ROOF RAFTERS DRILLED HOLES TO BIG NEED ROOF SUPPORT OR SISTER A BIGGER RAFTER
6) WALL BACKING MISSING EACH SIDE OF TOILET COMPARTMENT
7) OLD CEILING ELECTRIC IN BOX STILL HOT ?
8) NEW CEILING ELECTRIC WHERE DO EXISTING WIRE COME FROM ?, TOO MANY WIRES IN BOX
9) OUTLET AT TOILET NOT FASTENED TO WALL
10) TUB NOT INSTALLED, NO WATER TEST
11) TUB VENT BEFORE GOING HORIZONTAL WITH TUB VENT NEEDS TO BE 6" ABOVE FLOOD RIM TUB BLOCK OUT TO HAVE CONCRETE
12) NO DOOR FRAMING
13) NEED T & P LINE FOR H20 HTR
14) BEDROOM SOUTH OF BATH NOT DUCT FOR HVAC
-------------------------------------------------------------------------------------------------
NEW ADDITION:
1) ? TUB DOES IT HAVE A TRAP ?, NEEDS H20 TEST
2) CHECK ALL BANG PLATES
3) #12 ROMEX HANGING FROM SHOWER CEILING
4) ROMEX IN CLOSET CEILING NOT IN A BOX
5) POCKET DOOR NOT SECURED
6) NEW H20 HTR T & P AT GARAGE
7) EXHAUST FANS CLOSET/GARAGE NOT ON PLANS
8) RAN OUT FO ROOM NOT READY FOR INSPECTION