Permit: T04CM02123

Parcel: 125060250


Addresses:

2002 E 3RD ST

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
12/20/2004 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
1) INSTALL DBL REBAR ABOVE SOUTH GARAGE DOOR
12/17/2004 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) CANCEL PER CONTRACTOR
12/16/2004 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE DETAIL FOR STACK BLOCK CONNECTION AT ALL CORNERS
2) 12/R-S101 NOT COMPLIED WITH NO VERTICAL STEEL AND NO #4 'U' BARS
3) PROVIDE PROOF OF ? WALL AT 16" ON CENTER IT APPEARS TO BE AT 32" ON CENTER
12/10/2004 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) OK TO 6TH COURSE
12/09/2004 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) REBAR NOT INSTALLED
11/17/2004 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*/ 1) OK TO 5TH COURSE (BOND BEAM)