Permit: T04CM02121

Parcel: 13355231A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM02121

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/02/2004 ELECTRIC - ABOVE CEILING Approved
07/27/2004 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
POWER POLES FOR FURNITURE NOT IN
ELECTRICAL PANEL IN #111 NOT FINISHED FINISH WIRING INSTALL COVER
PANEL 101 2-M INSTALL ALL SCREWS ON COVER & BLANK OFF MISSING BREAKERS
SAME FOR PNL 1-M
IN ORDER TO RELEASE METERS 1-M AND 2-M THEY HAVE TO BE ON THE PERMIT
07/07/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) EXCEPT TITLE (REAR AREA)