Permit: T04CM02109

Parcel: 141174400

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM02109

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2004 FRAMING Approved IVRS - Inspection :*
07/27/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
07/23/2004 FRAMING Not ready for Inspection IVRS - Inspection :NEED SHEAR TRANSFER AT EAST SIDE OF GARAGE
07/21/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) TIGHTEN AB THRU-OUT IN ALL OF GARAGE 2) MOVE PEX 12" FROM CAN LIGHT MSTR BATH 3) SECURE AND ISOLATE FURN GAS FROM T & P 4) PUT #10 ROMEX AT FURNACE IN A BOX 5) BANG PLATE PEX LAUNDRY 6) PEX AT KITCHEN CAN LIGHT 7) BANG PLATE CONDUIT AND H2O BOTH ENDS FOR ISLAND 8) PLYWOOD SHEAR WALLS INSTALLED MAYBE 2 PLANS, AT DRYWALL INSP LEAVE THE RIGHT ONE 9) PLEASE CALL IN INSP 01025