Permit Number - T04CM02107
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2004 | MECHANICAL - FINAL | Approved | OK FOR FINAL C OF O | |
09/01/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection :CONDENSATE DRAIN PAN IS OVERFLOWING INSIDE THE A/C UNIT. A/C UNIT IS NOT LEVEL USE A BUSHING WHERE T-STAT WIRE ENTERS CABINET OF A/C UNIT MARK THE UNIT DATA PLATES W/PROPER HEAT STRIPINSTALLED & FUSE ACCORDINGLY PLANS CALL FOR CONTINUOUS BLEED-OFF FOR EVAP COOLERS. 3 COOLERS ARE NOT BLEEDING-OFF AND 2 ARE BLEEDING OFF INTO THE ROOF AND INTO THE PARKING LOT RESUBMIT TO ENGINEER 0R ARCH FOR DRAIN TERMINATION LOCATION. |
|
08/31/2004 | MECHANICAL - FINAL | Cancelled | PER CUSTOMER 621-9294 | |
08/31/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) INSPECTION CANCELLED |