Permit: T04CM02107

Parcel: 11004345C


Addresses:

3245 N SWAN RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/03/2004 MECHANICAL - FINAL Approved OK FOR FINAL C OF O
09/01/2004 MECHANICAL - FINAL Denied IVRS - Inspection :CONDENSATE DRAIN PAN IS OVERFLOWING INSIDE THE A/C UNIT. A/C UNIT IS NOT LEVEL
USE A BUSHING WHERE T-STAT WIRE ENTERS CABINET OF A/C UNIT
MARK THE UNIT DATA PLATES W/PROPER HEAT STRIPINSTALLED & FUSE ACCORDINGLY PLANS CALL FOR CONTINUOUS BLEED-OFF FOR EVAP COOLERS. 3 COOLERS ARE NOT BLEEDING-OFF AND 2 ARE BLEEDING OFF INTO THE ROOF AND INTO THE PARKING LOT
RESUBMIT TO ENGINEER 0R ARCH FOR DRAIN TERMINATION LOCATION.
08/31/2004 MECHANICAL - FINAL Cancelled PER CUSTOMER 621-9294
08/31/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) INSPECTION CANCELLED