Permit: T04CM02107

Parcel: 11004345C


Addresses:

3245 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/27/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*/AP-PROVIDE TESTING ON BACK FLOW DEVICE
08/04/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SHALL PROVIDE WATER TEST ON SYSTEM FOR WASTE AND VENT
08/03/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) WASTE AND VENT FOR RESTROOMS WATER TEST THRU ROOF OK. H20 PIPING FOR RESTROOM AREA 60 PSI AIR TEST OK. VENT FROM P4 + P8 AREA LEAKS WATER IN WALL AND WILL REQUIRE REPAIR AND RETEST. BREAK ROOM WASTE, VENT AND H20 PIPING OK