Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM02107
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*/AP-PROVIDE TESTING ON BACK FLOW DEVICE | |
08/04/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SHALL PROVIDE WATER TEST ON SYSTEM FOR WASTE AND VENT |
|
08/03/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WASTE AND VENT FOR RESTROOMS WATER TEST THRU ROOF OK. H20 PIPING FOR RESTROOM AREA 60 PSI AIR TEST OK. VENT FROM P4 + P8 AREA LEAKS WATER IN WALL AND WILL REQUIRE REPAIR AND RETEST. BREAK ROOM WASTE, VENT AND H20 PIPING OK |