Permit: T04CM02107

Parcel: 11004345C


Addresses:

3245 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM02107

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/24/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/23/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/NOT READY 1) MAIN BONDING JUMPER TO CONNECT TO GROUNDING ELECTRODE CONDUCTOR TERMANAL BAR. CAN NOT USE CAN AS A PATH TO GROUND. 2) BONDING JUMPERS T BE SIZED PER 250-02 & 250.66 3)BOND BUSHING NEEDS CONDUCTOR & BOND GUTTER ENCLOSURE 4) ANCHOR BOLT NOT INSTALLED 5) REJECTION PINS ARE NEEDED.
08/13/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) CANCELLED BY CONTRACTOR
08/04/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK RECESSED CANS IN SOFFITS
08/03/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) CANCELLED BY CONTRACTOR
07/29/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK 3/4" RIDGID AND 1 1/2" PVC BELOW GARAGE FLOOR 2) OK STUD WALLS
07/21/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :2-2" 1-4" 3-1" PVC INTRENCH TRANSMETER TO BUILDING
07/16/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK 1 1/2" PVC FOR ? UNDER SLAB-NOTE: YOU HAVE A LITTLE OVER 270 DEGREE SO FAR IN RUN
07/12/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK 3RD LIFT
07/01/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) SECURITY CABLE NOT LISTED FOR USE IN MORTAR 2) OK 1ST AND 2ND LIFTS