Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM02105

Parcel: 13319195A


Addresses:

6700 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
07/12/2004 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
07/08/2004 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*/ 1) BOND BUSHINGS NEEDED AT CONCENTRIC CROSSING 2) SUPPORT 2" PVC CONDUTIS BELOW DISCONNECTS 3) OK CONSTRUCTION POWER ONLY
06/17/2004 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*/ 1) WHERE IS SHELL PERMIT AND PLANS? 2) FILL UNUSED OPENINGS IN GUTTER. 3) BONDING JUMPERS TO BE SIZED PER 250-102 AND 250-66.