Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T04CM02101
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2004 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
07/02/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) GROUND ROD SYSTEM COVERED BEFORE INSPECTION, EXPOSE |
|
06/30/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NO UFER-PROVIDE GROUND ROD SYSTEM 2 GROUND RODS 8' AND 6' APART |