Permit: T04CM02097

Parcel: 11301037B


Addresses:

3915 N VINE AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/27/2004 BUILDING - FINAL Approved IVRS - Inspection :*
12/23/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) OK TO OCCUPY
2) WAITING ON FIRE INSPECTOR
3) NEED ALL CERTIFICATES
12/21/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU MUST HAVE FIRE SPRINKLER SYSTEM APPROVED BEFORE FINAL HOUSE APPROVAL
2) YOU MUST PROVIDE INSULATION, STUCCO AND POST TENSION ENGINEERING CERTIFICATES NOT LSI REPORT
12/17/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) LEAVE TUB THAT WAS USED FOR CAULKING F/PLACE LOG LITER
2) FINISH WIRING KITCHEN COUTNER OUTLETS
3) BLANK OFF BOTH OUTLETS BELOW KITCEHN COUNTER OVERHANG OUTLETS ARE NOT ALLOWED THERE
4) REMOVE TAPE AT H20 HTR FLUE SINGLE TO DBL WALL
5) HOOK UP AND FUSE HVAC UNIT ON ROOF
12/15/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) LATH EXPOSED AT REAR PARAPET GARAGE
3) NEED SCREWS IN W/HTR. FLUE JOINT ON ROOF (LOOSE)
4) NEED HVAC DISCONNECT FUSED 40/20 AMP
5) MISSING HOSE BIB VACCUM BREAKERS
6) EXPOSED WIRES AT PUMP 6) INSTALL 90 ON CONDENSATE LINE WEST WALL
7) CAULK LOG LITER, IN F/PLACE USE FIREPLACE CAULK NOT FIRECAULK
8) RAISE DISHWASHER DISPOSAL LINE AS HIGH AS POSSIBLE