Permit: T04CM02080

Parcel: 136312820

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
02/23/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
02/16/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHIM UNDER FLOOR TRUSSES
2) HTT16 MISSING EAST GARAGE DOOR
3) FINISH NAILING OSB FRONT PORCH
4) NO ROOF ACCESS
5) THERE APPEARS TO BE NO SPACING BETWEEN ROOF SHEATHING
02/11/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) FRONT ELEVATION NEED OUTRIGGERS AND RIBBON FIT GARAGE FRONT FOR CANTILIEVER
2) NEED HUS26 HANGER FOR FRONT ENTRY GIRDER TRUSS
3) WEST/NORTH CORNER NAIL IN ABS, ADD STRAP PROJECT
4) SHEAR WALL MISSED P.A. NORTH WALL AT SLIDING DOOR
5) REAR PORCH POST TO BEAM HARDWARE USE 16D COMMONS
6) 1ST FLOOR SHEAR WALL A.B. NOT INSTALLED PER SPACING
7) FIRST FLOOR GARAGE TO HOUSE G-4 SHEAR WALL MID SPAN BLOCKS
8) MISSING MANY NAILS SOME SHEETS TO MANY SHINNERS
9) G-3 SHEAR 2ND FLOOR NO CONNECTION DETAIL TO DRAG TRUSS IN PLAN SET, NEED INTERIOR DRYWALL SHEAR PLATE TO CONCRETE BOLT SCHEDULE
10) CROSS BRACE TRUSSES EACH END