Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T04CM02077

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/28/2004 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :* 1) PLEASE PROVIDE COPY OF LETTER FROM ARCH. CONSERVING SERVICE CHANGES FOR ELECTRICAL. OK TO CLEAR TEMP POWER FOR TEST SP # 130
10/18/2004 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) CORRECT ADDRESS ON SERVICE-SHOULD BE 2680 SPACE #130, USER FUSES PER PLAN 2) PANEL "P-1" (NEW) CALLS FOR 200 AMP MAIN BREAKER-SEE PLANS-A1C RATED AS SHOWN ON PLAN 1-LINE DIA 42 KA1C