Permit: T04CM02077

Parcel: 14042075B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM02077

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/03/2004 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT MC CABLE WITHIN 12' EACH TERMINATION, AND AT 6' INTERVALS PER NEC. USE LISTED STRAPS, BUNDLING WITH TY WIRE NOT APPROVED ABOVE CEILING, SHOULD BE CLAMPED TO CEILING WIRE WITH APPROVED DEVICE