Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/03/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT MC CABLE WITHIN 12' EACH TERMINATION, AND AT 6' INTERVALS PER NEC. USE LISTED STRAPS, BUNDLING WITH TY WIRE NOT APPROVED ABOVE CEILING, SHOULD BE CLAMPED TO CEILING WIRE WITH APPROVED DEVICE |