Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/04/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) FRAMING TO BE APPROVED WHEN BREAK THROUGH TO TV IS INSPECTED 2) OK TO INSULATE |
|
| 12/29/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TO BE APPROVED WHEN ALL OTHER TRADES ARE COMPLETED 2) COMPLETE OPENING TO TV ROOM 3) HAVE GAS REVISION FOR USE OF CORRIGATED GAS LINE 4) PROVIDE PRESSURE TEST TO GAS LINE 5) PROVIDE TEST UNABLE TO LOCATE GAUGE |
|
| 12/21/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CEILING LIGHT WIRES MUST TERMINATE IN APPROVED BOXES 2) PROVIDE A DRAIN WASTE VENT WATER TEST TO ROOF PER UPC 3) BREAK THRU TO EXISTING HOUSE NOT MADE 4) SMOKE DETECTOR REQUIRED IN FOYER LEADING TO BEDROOM AND IN BEDROOM 5) INSULATE ALL DUCT "Y" IN CONFINED SPACE 6) DUCTS RESTRICTED BY SHARP ? AND FRAME AND BY OUTSIDE UNIT 7) HAVE GAS PLAN REVISED FOR USE OF CORRIGATED STAINLESS STEEL PIPE 8) NAIL POST CAPS 9) WATER HEATER VENT MUST EXTEND 1 FEET HIGHER THAN VERTICAL WALL SURFACE WITHIN 10 FEET 10) NO GAS PRESSURE TEST LOCATED 11) STOPPED INSPECTION, TO MANY ITEMS |