Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 07/02/2004 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) YOU HAVE CODE VIOLATIONS IN SERVICE PANEL A) ALL BREAKERS TO BE BRYANT TYPE B) BACK FED MAIN NEEDS A HOLDOWN DEVICE C) PLEASE LEAVE A LOAD CALC ON SITE FOR SERVICE (BOX RATED AT 25 AMP) D) INSTALL GRD BUSS AT SUB/PANEL, NEUTRALS TO ISOLATED BAR, REMOVE BOND SCREWE) COULD NOT LOCATE HOME RUNS IN SERVICE FOR NEW SUB-PANEL F) ONLY ONE SPACE LEFT IN SERVICE G) TAPE ? DUCT TOGETHER CLAMP WASN'T HOLDING IT SECURE |