Permit: T04CM02068

Parcel: 123050380


Addresses:

2165 E EDISON ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM02068

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/02/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) YOU HAVE CODE VIOLATIONS IN SERVICE PANEL A) ALL BREAKERS TO BE BRYANT TYPE B) BACK FED MAIN NEEDS A HOLDOWN DEVICE C) PLEASE LEAVE A LOAD CALC ON SITE FOR SERVICE (BOX RATED AT 25 AMP) D) INSTALL GRD BUSS AT SUB/PANEL, NEUTRALS TO ISOLATED BAR, REMOVE BOND SCREWE) COULD NOT LOCATE HOME RUNS IN SERVICE FOR NEW SUB-PANEL F) ONLY ONE SPACE LEFT IN SERVICE G) TAPE ? DUCT TOGETHER CLAMP WASN'T HOLDING IT SECURE