Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM02068
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/02/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) YOU HAVE CODE VIOLATIONS IN SERVICE PANEL A) ALL BREAKERS TO BE BRYANT TYPE B) BACK FED MAIN NEEDS A HOLDOWN DEVICE C) PLEASE LEAVE A LOAD CALC ON SITE FOR SERVICE (BOX RATED AT 25 AMP) D) INSTALL GRD BUSS AT SUB/PANEL, NEUTRALS TO ISOLATED BAR, REMOVE BOND SCREWE) COULD NOT LOCATE HOME RUNS IN SERVICE FOR NEW SUB-PANEL F) ONLY ONE SPACE LEFT IN SERVICE G) TAPE ? DUCT TOGETHER CLAMP WASN'T HOLDING IT SECURE |