Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM02058
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/25/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/APPROVED-OK FOR FINAL C OF O | |
08/19/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED-1)PROVIDE A FRESH AIR INTAKE AS PER PLANS. 2) #10 WIRE NOT ADEQUATE FOR 40 AMP. RECALL FOR INSPECTION |
|
08/05/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE A LADDER THAT WILL REACH THE TOP OF THE ROOF |