Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM02058
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/APPROVED-OK FINAL | |
08/27/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection :PLAN REVISIONS NOT CITY STAMPED APPROVED | |
08/25/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection. Items #4 and 6 of previous inspection not complete |
|
08/19/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/DENIED-ROOF 1)EXHAUST FAN NOT HOOKED UP 2)TIGHTEN ALL SCALTITE? FITTINGS 3)FUSES TO MATCH WIRE AMPANTY? 4)REJECTION PINS NEEDED AT SERVICE 5)GROUND CARDECTOR MISSING LUG 6)MAN CIRCUIT BRAKER NOT AS PER PLANS |
|
08/05/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO HAVE APPROVED EXTENDER RINGS 370.20 METAL NOT APPROVED 2) PLEASE PROVIDE ROOF ACCESS |