Permit: T04CM02031

Parcel: 10816008G


Addresses:

4910 N 1ST AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
08/18/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/ 1) CORRECTIONS MADE OK, OK TO COVER ALL AREAS 2) REVISED PLANS ON SITE
07/23/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :PLUMBING IS PER ARCHITECT LETTER DATED 7-21-04. lETTER IS NOT APPROVED BY COT PLAN CHECK. LETTER MUST BE APPROVED
07/20/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :NEED CORRECT TYPE OF MATERIAL, PLAN CALLS FOR CASR IRON UNDERGOUND OR PROVIDE STAMPED LETTER FROM ENGINEER STATING PVC SCH40 DWV OK FOR ROUGH SOIL
PROVIDE CORRECT TRANSITION COUPLING FOR ABS TO PVC GREEN GLUE NOT ACCEPTABLE
07/16/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) 1 1/2" HORIZONTAL VENT EXCEEDS ALLOWABLE LENGTH VENT MUST BE INCREASED ONE PIPE SIZE FOR IT'S ENTIRE LENGTH 2) UNDERGROUND NOT INSTALLED PER PLAN-SEE DETAIL P-1