Permit: T04CM02030

Parcel: 138170190


Addresses:

322 E TETON RD #01

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/20/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/1)SOIL WATER TEST IS OK 2)ALL CORRECTIONS HAVE BEEN MADE. 3) OK TO BACKFILL TRENCH
12/15/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)CAN NOT LOCATE A 1/4 BEND IN A HORIZONTAL POSITION ON TUB TRAP ARMS. THESE MUST BE L-SWEEPS 2)RE TEST THE SYSTEM
12/10/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)CAN NOT WET VENT A 2" TRAP ON A 2" BARREL. THE BARREL SHALL BE AT LEAST ONE PIPE SIZE LARGER THAN TRAP ARM ON EAST UNIT 2)NOTE: WEST UNIT IS OK FOR BACKFILL ONLY